X-317™ | Specifications
Each channel can be programmed to output a voltage or current; however, unlike most PLCs, the X-317 is designed for web-based applications from the ground up.
Specifications
Power Requirements
- Voltage: 9-28VDC
- Max Current: (table)
10 Mbps Network Speed
Power Supply | Outputs = 0V | Outputs = 20mA |
---|---|---|
9 VDC | 210 mA | 404 mA |
12 VDC | 162 mA | 298 mA |
24 VDC | 92 mA | 163 mA |
100 Mbps Network Speed
Power Supply | Outputs = 0V | Outputs = 20mA |
---|---|---|
9 VDC | 302 mA | 498 mA |
12 VDC | 229 mA | 368 mA |
24 VDC | 126 mA | 198 mA |
Analog Outputs
- Number of channels: 5 (Individually configurable)
- Output Ranges: 0-5V, 0-10V, ±5V, ±10V, 4-20mA (software selectable)
- Resolution: 16-bit DAC (0-65535)
- Linearity Error: ±1-count, monotonic DAC
- Current Output (Voltage Mode): 10mA max (min load = 1K), 30mA max short circuit
- Voltage Output Inaccuracy: ±0.2% FSR includes offset error, gain error and non-linearity error, -40 to 65°C
- Max Load Capacitance: 20nF (no load), 5nF (1K load)
- Current Output Range: 4-20mA
- Current Output Inaccuracy: ±0.2% FSR includes offset error, gain error and non-linearity error, -40 to 65°C
- Output Compliance Voltage: 11.50V min (max loop voltage)
- Isolated Power Supply: Internal DC-DC converter
- Isolation: Galvanic, 1500 VAC
- ESD Protection: Integrated 15kV protection (IEC61000-4-2)
- Output Protection: Integrated over-temperature, open-line and short circuit protection
- Output Alarms: Open current loop, high internal temperature
- Load Type: Grounded, COM of all 5-channels are connected together
- Output at power up: Programmable
Network
- Type: 10/100 Base-T Ethernet Port
- Setup: Static IP address assignment or DHCP, HTTP port selectable
NONVOLATILE MEMORY
- All user settings are stored in nonvolatile memory. Settings will not be lost when power is disconnected.
Connectors
- Power, & Outputs: 12-Position, 3.81mm terminal spacing, Removable. For 16-28 AWG wire.
- Network: 8-pin RJ-45
LED Indicators
- Number of LEDs: 8
- Power on
- Fault condition (channels 1-5)
- Network linked
- Network activity
Physical
- Operating Temperature: -40°F to 150°F (-40°C to 65.5°C)
- Storage Temperature: -40°F to 185°F (-40°C to 85°C)
- Size:
- 1.41in (35.7mm) wide
- 3.88in (98.5mm) tall
- 3.1in (78mm) deep (not including connector)
- Weight: 4.8 oz (136 g)
- Enclosure Material: Lexan 940 Polycarbonate Plastic
- Enclosure Flame Rating: UL94 V0
Protocols
- HTTP, XML, Modbus TCP/IP
Password Settings
- Password protection on setup page: Yes
- Password protection on control page: Optional
- Password Encoding: Base 64
- Password Length: 13 Characters
Electromagnetic Compliance
- IEC CISPR 22, CISPR 24
- FCC 47CFR15 (Class B)
- EN55024 ITE Immunity (2010)
- EN55022 Emissions (2010)
Product Safety Compliance
- IEC 61010-1



More Information:
ManualsWhere to Buy
Click "Buy Online" to view part numbers and pricing. X-317 is available inthe USA and internationally, and can be purchased either from us or an Authorized Distributor.