X-405™ | Specifications
The X-405 is a rock solid drop-in temperature and/or humidity monitoring solution.
Specifications
Power Requirements
- Voltage:
- X-405-I: 9-28 VDC
- X-405-E: POE and/or 9-28 VDC
- Max Current: 134mA
Temperature Sensors
- Maximum Number of Sensors: 16
- Type: Digital 1-Wire (Maxim Semiconductor DS18B20)
- Temperature Range: -67°F to 257°F (-55°C to +125°C)
- Accuracy: ±0.5°C (from -10°C to +85°C)
- Sensor Functions: Monitor Temperature, Log Temperature, Email Alerts, SNMP Traps
- Humidity Type: Xytronix Model X-DTHS-P sensor
- Humidity Range: 0-100% RH
- Accuracy: ±2%
- Max Cable Length: 600 feet (180m) maximum combined cable length
Real-Time Clock:
- Manual or NTP(Network Time Protocol) setup
- NTP Sync Period: Once, Daily, Weekly, On Powerup
- Auto Daylight Savings Adjustment
- Battery (capacitor) Power Backup
Capacitor Power Backup
- Backup Functions: Retain Real-Time Clock, 1 Register, 2 Counters, 4 Relay States
- Backup Duration: 24 hours
Network
- Type: 10/100 Base-T Ethernet Port
- Setup: Static or DHCP IP address configuration
Connectors
- Power and 1-Wire Bus: 5-Position, 3.81mm terminal spacing, Removable. For 16-28 AWG wire.
- Network: 8-pin RJ-45
LED Indicators
- Number of LEDs: 3
- Power on
- Network linked
- Network activity
Physical
- Operating Temperature: -40°F to 150°F (-40°C to 65.5°C)
- Size:
- 1.41in (35.7mm) wide
- 3.88in (98.5mm) tall
- 3.1in (78mm) deep (not including connector)
- Weight: 5 oz (142 grams)
- Enclosure Material: Lexan 940 Polycarbonate Plastic
- Enclosure Flame Rating: UL94 V0
Protocols
- HTTP, HTTPS, SSL, XML, Modbus TCP/IP, SNMP V1,2C,V3, SMTP
Logging
- Log File Size: 3,072-Kbyte (up to 50,688 logs)
- Storage: Nonvolatile Flash
- Buffer Architecture: Circular Buffer
Log data can be periodically stored on a computer via FTP or email.
Advanced Features
- Task Builder
- BASIC interpreter (up to 4-Kbytes script file size)
- Remote services
Password Settings
- Password Length: 6-18 Characters
Electromagnetic Compliance
- IEC CISPR 22, CISPR 24
- EU EN55024, EN55022
- X-405-I: FCC 47CFR15 (Class B)
- X-405-E: FCC 47CFR15 (Class A)
Product Safety Compliance
- IEC 61010-1



More Information:
ManualsWhere to Buy
Click "Buy Online" to view part numbers and pricing. X-405 is available inthe USA and internationally, and can be purchased either from us or an Authorized Distributor.