ControlByWeb
Product Catalog   (435) 750-5999
X-408 Web-Enabled 8 Digital Input Module | ControlByWeb

X-408 features 8 digital inputs and a built-in web-server.

Specifications

Power Requirements

  • Voltage:
    • X-408-I: 9-28 VDC
    • X-408-E: POE and/or 9-28 VDC
  • Max Current: 240mA

Digital Inputs

  • Number of Inputs: 8
  • Type: Optically-Isolated
  • Voltage Range: 4-26VDC
  • Current: 950uA @ 4V, 8.5mA @ 26V
  • Minimum Hold Time: 20ms
  • Input Functions: Monitor State, Control Relays, Control Remote Relays, Scalable Counter, On Timer, Total On Timer, Frequency
  • Maximum Count: 24-bit
  • Max Count Rate: 200Hz Max (Dependent on Configuration)
  • Edge Trigger: Rising, Falling or Both

Real-Time Clock:

  • Manual or NTP(Network Time Protocol) setup
  • NTP Sync Period: Once, Daily, Weekly, On Powerup
  • Auto Daylight Savings Adjustment
  • Battery (capacitor) Power Backup

Capacitor Power Backup

  • Backup Functions: Retain Real-Time Clock, 1 Register, 2 Counters, 4 Relay States
  • Backup Duration: 2 week minimum

Network

  • Type: 10/100 Base-T Ethernet Port
  • Setup: Static or DHCP IP address configuration

Connectors

  • Power and Inputs: 14-Position, 3.81mm terminal spacing, Removable. For 16-28 AWG wire.
  • Network: 8-pin RJ-45

LED Indicators

  • Number of LEDs: 11
    • Power on
    • Digital Inputs 1-8
    • Network linked
    • Network activity

Physical

  • Operating Temperature: -40°F to 150°F (-40°C to 65.5°C)
  • Size:
    • 1.41in (35.7mm) wide
    • 3.88in (98.5mm) tall
    • 3.1in (78mm) deep (not including connector)
  • Weight: 5 oz (142 grams)
  • Enclosure Material: Lexan 940 Polycarbonate Plastic
  • Enclosure Flame Rating: UL94 V0

Protocols

  • HTTP, HTTPS, SSL, XML, Modbus TCP/IP, SNMP, SMTP, Remote Services

Logging

  • Log File Size: 512K (up to 8,448 logs)
  • Storage: Nonvolatile Flash
  • Buffer Architecture: Circular Buffer
  • Log data can be periodically stored on a computer via FTP or email.

Advanced Features

  • Task Builder
  • BASIC interpreter
  • Remote services

Password Settings

  • Password Length: 6-18 Characters

Electromagnetic Compliance

  • IEC CISPR 22, CISPR 24
  • EU EN55024, EN55022
  • X-408-I: FCC 47CFR15 (Class B)
  • X-408-E: FCC 47CFR15 (Class A)

Product Safety Compliance

  • IEC 61010-1
CE listed RoHS compliant Made in the USA