Specifications

Power Requirements

  • Voltage: 9-28 VDC (24V recommended)*
  • Max Current: See table below for typical values at 25°C.
Power Supply All Relays OFF All Relays ON
9 VDC 18 mA 1200 mA
12 VDC 14 mA 880 mA
24 VDC 11 mA 450 mA

Relay Contacts

  • Number of Relays: 10
  • Max Voltage: 277VAC, 30VDC
  • Max Current: 15A
  • Contact Type: SPDT (Form C)
  • Load Type: General Purpose
  • Contact Resistance: < 30 milliohms initial
  • Contact Material: AgSnO2
  • Electrical Life: 100K cycles (Typical)
  • Mechanical Life: 10M cycles (Typical)
  • Environmental Rating: Over voltage Category II, Pollution Degree 2
  • Relay Modes: ON/OFF or Pulse
  • Pulse Timer Duration: 0.1 to 86,400 Seconds (1-day)

Connectors

  • Expansion Connector: Ribbon cable, 2x5-position, polarized 0.100" pitch
  • Relays: 1/4" tab connectors

LED Indicators

  • Number of LEDs: 11
    • Power on
    • Relays 1-10

Physical

  • Size:
    • 8.60in (218.44mm) wide
    • 4.95in (125.73mm) tall
    • 2.46in (62.48mm) deep
  • Weight: 20 oz (566 g)
  • Enclosure Material: PVC
  • Enclosure Flame Rating: UL94 V1

Environmental

  • Operating Temperature: -40°F to 150°F (-40°C to 65.5°C)
  • Storage Temperature: -40°F to 185°F (-40°C to 85°C)
  • Humidity: 5-95%, non-condensing
  • Altitude: Up to 2,000m
  • Indoor use or NEMA-4 protected location

Electromagnetic Compliance

  • IEC CISPR 22, CISPR 24
  • FCC 47CFR15 (Class B)
  • EN55024 ITE Immunity (2010)
  • EN55022 Emissions (2010)

Product Safety Compliance

  • IEC 61010-1
CE listed RoHS compliant Made in the USA

* This device is sold as a component and does not include a power supply. The X-18s, X-19s, and X-20s expansion modules are not powered through the expansion bus cable and require separate wiring to the power supply. They may share the same power supply that is used to power the X-400 or X-600M controller or they may use separate power supplies. Please use the same power supply voltage for all devices on the expansion bus (24V recommended).


More Information:

Manuals

Where to Buy

Click "Buy Online" to view part numbers and pricing. X-18s is available inthe USA and internationally, and can be purchased either from us or an Authorized Distributor.

Subtotal

SECURE CHECKOUT

Your cart is empty.


Your Cart is currently empty.


View Return Policy View Cart